Page 9 Once the correct pass-code has been entered, the display shows 'SYS CH', with 'CH' blinking. At this point the oper
Page 10 CHANNEL CONFIGURATION After entering correct pass-code and selecting the blinking 'CH' (ref. SETUP section), the display shows
Page 11 key and then pushing it again will decrement the value (^v key works as a toggle -- alternating between increment and decrement). To chang
Page 12 SETPOINT value. Once the desired SETPOINT value is displayed, push SETUP key to enter that value and go on to setup channel 1's oper
Page 13 Setup For Engineering Units After setting a channel's relay for NORMALLY OPEN/CLOSED operation, the next parameter to be set are the
Page 14 Example #2: Use of the LOW SCALE Parameter Setup for a 4-20ma transducer signal corresponding to 500-2000 degrees Fahrenheit temperature i.
Page 15 Setup For Relay Latch/Non-Latch After setting DISPLAY TIME, the next parameter determines whether the output relays will operate in a Latc
Page 16 desired value is displayed, push SETUP key to enter that value and go to the next step. Voltage Range Setup (for millivolt inputs) For M
Page 17 PEAKS A very useful function of DPS3000 is tracking the highest (peak) and the lowest (valley ) point attained by each channel. This is p
Page 18 DPS3207 7 Channel Unit DPS3204 4 Channel Unit ENTER PASSCODE -- 3254 SYS CH SELECT CHANNEL IP TYPE DISPLAY OPTION (Select one) ELAPSED
TABLE OF CONTENTS Page 1 SPECIFICATIONS ...
Page 19 DPS3107 7 Channel Unit DPS3104 4 Channel Unit ENTER PASSCODE -- 3254 SYS CH SELECT CHANNEL IP TYPE DISPLAY OPTION (Select one) ELAPSED
Page 20 RATE DPS3000 series tracks the rate of process change/minute for each channel. This rate is displayed by first pushing the CH. SEL key
Page 21 NOTE: LOOK UNDER SPECIFICATIONS FOR THE RATING ON RELAYS AND OPEN COLLECTOR OUTPUTS. UNDER NO CONDITION SHOULD THE RELAYS AND OPEN C
Page 22 1 2 3 4 6 5 7 8 9 1011121314OUTPUT CONNECTOR PIN ASSIGNMENT - + - + - +
Page 23 TROUBLE SHOOTING If the meter locks on a particular display, unplug and plug in again to unlock the display. A total reset defaults all sc
Page 24 MOUNTING 3.70” (94mm) 4.05 ” (10 2.87 mm) 1.77” (45mm) 0.15” dia. (3.81mm) Figure - 4. Panel Cutout and mounting hole
Page 25 WARRANTY For Warranty information, check Omega’s web site at http://www.omega.com
Page 26
Page 27
Page 28
TABLE OF CONTENTS Page 2 Electro-Mechanical Relay Option ...
Page 3 SPECIFICATIONS (Typical @ 25C and rated supply voltage unless otherwise specified) STANDARD INPUTS * 4-20ma 10-50ma 0-5Vdc 0-10V
Page 4 DESCRIPTION DPS3000 Series instruments are multi-channel scanners that pack a number of functions into one unit. Tasks that require
Page 5 DISPLAYING PARAMETERS DPS3000 Series keeps track of various parameters and these may be displayed by pushing appropriate keys on the front
Page 6 setpoint, difference between any two selected channels or just run as a timer. In the timer mode the unit keeps track of process run time
Page 7 Display time for each channel is programmable from 1-999 seconds (16.65 min.). This is useful for adjusting display time to a rate which i
Page 8 a) The first one is a momentary display in which the deviation is indicated for a short time. Following this brief display time, the u