Process/Strain Gauge Controller Manual
CNiS8, CNiS8C,
CNiS8DH, CNiS8DV,
CNiS16, CNiS16D, CNiS32
Page view 0
1 2 3 4 5 6 ... 71 72

Summary of Contents

Page 1 - User’s Guide

User’s Guideomega.come-mail: [email protected] info:omega.com/specs/iseriesFor latest product manualsomegamanual.info®®Shop on line atUSAMADE INPr

Page 2 - Servicing Europe:

Figure 2.3 Rear Panel Input ConnectionsTable 2.2 Rear Panel ConnectorPOWER AC/DC Power Connector: All modelsINPUTInput Connector:All models PR (Proce

Page 3 - ...22

2.3 Electrical Installation2.3.1 Power ConnectionsCaution: Do not connect power to your device until you have completed allinput and output connection

Page 4

2.3.2 Process CurrentThe figure below shows the wiring hookup for Process Current 0 – 20 mA.Figure 2.5 Process Current Wiring Hookup(Internal and Exte

Page 5

2.3.4 Strain Gauge The figure below shows the wiring hookup for 4-wire bridge input.Figure 2.7a) 4-Wire Voltage/Bridge Input b) 4-Wire Bridge Input w

Page 6

2.3.4 Strain Gauge (continued)The figure below shows Voltage (bridge withamplified output) input with internal excitation.Where:+S: signal plus-S: sig

Page 7

2.3.5 Wiring Outputs (continued)This device may also have a programmable communication output. The RS-232and RS-485 Output Connection are shown below.

Page 8

2.3.5 Wiring Outputs (continued)This meter is capable of supplying 5 or 10 Vdc sensor excitation. The excitationoutput connection and location of S2 p

Page 9 - Guide for assembly and

PART 3OPERATION: CONFIGURATION MODE3.1 IntroductionThe instrument has two different modes of operation. The first, Run Mode, isused to display values

Page 10

3.2 Menu ConfigurationIt is required that you put the controller in the Standby Mode for anyconfiguration change other than Set Points & Alarms.Fi

Page 11

3.2.1 ID Number MenuSEE ID MENU SELECTION IN CONFIGURATION SECTION FORENABLE/DISABLE OR CHANGE ID CODE. If ID Code is Disabled or set as Default (0000

Page 12

It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its pr

Page 13

3.2.2 Set Points MenuSETPOINT 1:Press a 1) Press a, if necessary until SP1prompt appears.Press d 2) Display shows previous value of “Setpoint 1” with

Page 14

3.2.3 Configuration MenuFigure 3.2 Flow Chart for Configuration MenuEnter Configuration Menu:Press a 1) Press a, if necessary, until CNFGprompt appear

Page 15

ENTER INPUT TYPE MENU:Press a 1) Press a, if necessary, until CNFGprompt appears.Press d 2) Display advances to INPTInput Menu.Press d 3) Display flas

Page 16 - 8 DIN Compact Unit

BUTTON SELECTION SUBMENU:Press d 12) Display flashes previous selection of GROSGross or PEAKPeak.Press b 13) Scroll through the available selection GR

Page 17

ENTER READING CONFIGURATION MENU:Press a1) Press a, if necessary, until CNFGprompt appears.Press d2) Display advances to INPTInput Menu.Press a3) Disp

Page 18 - 3.2 Menu Configuration

FILTER CONSTANT SUBMENU:Press d14) Display flashes previous selection for Filter Constant.Press b15) Scroll though the available selections: 0001,0002

Page 19

3.2.6 Input/Reading (Scale and Offset) MenuInput voltage or current can be converted or scaled into values appropriate forthe process or signal being

Page 20

Max scale should not be more than 50% FS because of noise relatedissues.Press d27) Display flashes STRDstored message momentarily and thenadvances to

Page 21

Determine IN!1 and IN!2 Input Range and Resolution. For our transducer select0 ~ 100 mV range and LOW resolution (10 µV)IN!1 = 0 (mV) X 100 (cts/mV) x

Page 22

Example 3: Scaling with Current/Voltage Transducer (Process) Input. The following example include details for a specific scenario inwhich a 4 - 20 mA

Page 23

TABLE OF CONTENTSPart 1: Introduction...21.1 Description ...

Page 24

3.2.7 Alarm 1 MenuThis unit is equipped with two physical outputs that can only be configured asfollows: Alarm 1 & Alarm 2, Alarm 1 & Output 2

Page 25

ALARM 1 ENABLE/DISABLE SUBMENU:Press b 5) Scroll though the available selection until ENBLdisplays touse Alarm 1.Press d6) Display shows STRDstored

Page 26

CONTACT CLOSURE SUBMENU:Press d11) Display flashes previous selection. Press b to N.ç.. NormallyClosed or N.o.. Normally Open.Press d12) Display sho

Page 27

ALARM ENABLE/DISABLE AT POWER ON:Press d15) Display flashes previous selection. Press bto ENBLenableor DSBLdisable.Press d16) Display shows STRDstor

Page 28

3.2.8 Analog Output (Retransmission) MenuAnalog Output can be configured as Retransmission or Control outputs.In this section we will discuss Retransm

Page 29

31ANALOG OUTPUT ENABLE/DISABLE SUBMENU:Press b5) Scroll though the available selection until ENBLdisplays touse Analog Output Retransmission (output p

Page 30

Accuracy of Analog Output board is +/-1% of FS (Full Scale) when followingconditions are satisfied:1. The input is not scaled below 1% of Input FS (10

Page 31

3.2.9 Alarm 2 MenuThis unit is equipped with two physical outputs that can only be configured asfollows: Alarm 1 & Alarm 2, Alarm 1 & Output 2

Page 32

34ALARM 2 ENABLE/DISABLE SUBMENU:Press d5) Display flashes previous selection. Press buntil ENBLdisplays to use Alarm 2.Press d6) Display shows STRD

Page 33

LOOP BREAK ENABLE/DISABLE SUBMENU:Press d4) Display advances to Loop Break Time ENBLEnable or DSBLDisable Submenu and flashes the previous selection.

Page 34

LIST OF FIGURES:Figure 2.1 Front Panel Display ...5Figure 2.2 Rear Panel Power and O

Page 35

3.2.11 Output 1 MenuAlarm 1 and Output 1 or Analog Output (Retransmission) share the same contactson the rear panel connector. If Alarm 1 or Analog Ou

Page 36

37ENTER OUTPUT 1 MENU:Press a1) Press a, if necessary, until CNFGprompt appears.Press d2) Display advances to INPTInput Menu.Press a3) Press a, if

Page 37

MAXIMUM/PERCENT HIGH SUBMENU:Specify in percent, the maximum value (99) for control output. If the output isanalog proportional (Current or Voltage),

Page 38

ACTION TYPE SUBMENU:The error that results from the measurement of the Process Variable may bepositive or negative since it may be greater or smaller

Page 39

If Anti Integral (Anti Windup) Submenu “Enabled”, this feature allows the error term outside the proportional band to be calculated andaccumulated for

Page 40 - It is required that you put

RESET SETUP SUBMENU:Press d33) Display flashes 1stdigit of the previous IRESTReset value.Press b& c34) Press band cbuttons to enter a new “Reset

Page 41

DAMPING FACTOR SUBMENU:Press d42) Display flashes the previous “Damping Factor” selection.Press b43) Scroll through the available selections: 0000,0

Page 42

3.2.12 Output 2 MenuOutput 2 and Alarm 2 share the same contacts on the rear panel connector. IfAlarm 2 is Enabled, Output 2 is automatically Disabled

Page 43

ACTION TYPE SUBMENU:The error that results from the measurement of the process variable may bepositive or negative since it may be greater or smaller

Page 44

CYCLE TIME SUBMENU:Press d15) Display flashes 1stdigit of the previous “Cycle Time” value.Press b& c16) Press band cbuttons to enter a new “Cycl

Page 45

NOTES, WARNINGS and CAUTIONSInformation that is especially important to note is identified by following labels:• NOTE • WARNING or CAUTION• IMPORTANT•

Page 46

3.2.13 Ramp & Soak MenuAlarm must be DISABLED if Ramp is ENABLED.Figure 3.11 Flow Chart for Ramp and Soak MenuENTER RAMP AND SOAK MENU:Press a1)

Page 47

SOAK ENABLE/DISABLE SUBMENU:Press d7) Display flashes ENBLor DSBL.Press b8) Scroll through the available selections: “Enable” or “Disable”.Press d9

Page 48

3.2.14 ID Code MenuFigure 3.12 Flow Chart for ID Code MenuENTER ID CODE MENU:Press a1) Press a, if necessary, until CNFGprompt appears.Press d 2) Di

Page 49

ENTERING OR CHANGING YOUR (DEFAULT) ID CODE:Enter IDmenu (Repeat steps from 1 to 3).Press d10) Display advances to CH.IDChange ID Code Submenu.Press

Page 50

3.2.15 Communication Option MenuPurchasing the controller with Serial Communications permits an instrument to be configured or monitored from an IBM P

Page 51

ENTER COMMUNICATION OPTION MENU:Press a1) Press a, if necessary, until CNFGprompt appears.Press d2) Display advances to INPTInput Menu.Press a 3) P

Page 52

STOP BIT SUBMENU:Press d15) Display flashes previous selection for “Stop Bit”.Press b16) Scroll through the available selections: 1-BIT, 2-BIT.Press

Page 53

Press d25) Display flashes previous selection for “Echo”.Press b26) Scroll through the available selections: NO, YES.Press d27) Display flashes STRDst

Page 54 - ** Valid only for -C24

DATA FORMAT SUBMENU:Preformatted data can be sent automatically or upon request from the controller.Use the Data Format Submenus to determine what dat

Page 55

55UNIT SUBMENU (not applicable):Press d50) Display flashes previous selection for UNIT.Press b51) Scroll through the available selections: NO, YES.P

Page 56

PART 1INTRODUCTION1.1 DescriptionThis device can be purchased as monitor (read process value only) or asa controller.• The i Series Strain and Process

Page 57

3.2.16 Display Color Selection MenuThe menu below allows the user to select the color of the display.Figure 3.14 Flow Chart for Display Color Selectio

Page 58

ALARM 2 DISPLAY COLOR SUBMENU:Press d11) Display flashes previous selection for “Alarm 2 Color Display”.Press b12) Scroll through the available sele

Page 59

Example 3:Output 1 = Analog Output (Alarm 1 disabled), Setpoint 1 = 300,Output 2 = Relay, Setpoint 2 = 200Alarm 1 & 2 Setup: Deviation, Band, “ALR

Page 60

59Linearization PointsUp to 10 Linearization PointsConfigurationSingle-endedPolarityUnipolarStep Response0.7 sec for 99.9%Decimal SelectionNone, 0.1,

Page 61

60Cycle Time1 to 199 seconds; set to 0 for on/offoperationGain0.5 to 100% of span; Setpoints 1 or 2Damping0000 to 0008Soak00.00 to 99.59 (HH:MM), or o

Page 62

61ApprovalsUL, C-UL and see CE Approval SectionGENERALLine Voltage/Power90-240 Vac +/-10%, 50-400 Hz*110-375 Vdc, equivalent voltage4 W power for iS8,

Page 63 - Adjustment

62PART 5FACTORY PRESET VALUESTable 5.1 Factory preset valueMENU ITEMS FACTORY PRESET VALUES NOTESSet Point 1 (SP1) 000.0Set Point 2 (SP2) 000.0Input:I

Page 64

63MENU ITEMS FACTORY PRESET VALUES NOTESPID:PID Auto (AUTO) Disable (DSBL)Anti Integral (ANTI) Disable (DSBL) Output 1 onlyProportion Value (PROP) 020

Page 65 - (Low Voltage/Power Option)

64PART 6CE APPROVALS INFORMATIONThis product conforms to the EMC directive 89/336/EEC amended by93/68/EEC, and with the European Low Voltage Directive

Page 67

1.2 Safety ConsiderationsThis device is marked with the international caution symbol. It isimportant to read this manual before installing or commissi

Page 68

NOTES66

Page 69

WARRANTY/DISCLAIMEROMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) yearfrom the

Page 70

M3540/1106Where Do I Find Everything I Need for Process Measurement and Control? OMEGA…Of Course!Shop on line at omega.comTEMPERATUREThermocouple, R

Page 71 - , omega.com

1.3 Before You BeginInspecting Your Shipment:Remove the packing slip and verify that you have received everythinglisted. Inspect the container and equ

Page 72 - Shop on line at omega.com

PART 2SETUP2.1 Front PanelFigure 2.1 Front Panel DisplayTable 2.1 Front Panel Annunciators1 Output 1/Setpoint 1/ Alarm 1 indicator2 Output 2/Setpoint