Omega DPF76 User Manual Page 25

  • Download
  • Add to my manuals
  • Print
  • Page
    / 30
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 24
20
PROBLEM SOLUTIONSPOSSIBLE CAUSES
TROUBLESHOOTING GUIDE
Power is applied to unit but the display
does not light.
Unit works, but occasionally the display
freezes or skips counts.
Input signal is connected but the unit
does not count or display rate.
Rate is displaying: r FFFFF.
Relays are not activating properly.
Counter resets before reaching 999999.
Various menu items are not being
displayed.
1. AC or DC power wiring is incorrect.
1. Line noise is affecting the processor
due to a current spike or surge.
1. Input wiring is incorrect.
2. Scale factors are incorrect.
3. Transmitting device is defective.
4. Wrong debounce filtering selected.
5. Unit is defective.
1. The unit is trying to display a
number which it can't (too small or
too large).
2. Line noise affected unit on power
up.
1. Wrong relay duration.
2. Relay set for wrong activation
i.e. count instead of rate.
1. Relay duration is set at a value other
than 00.0. This causes the counter
to auto-reset at the preset.
1. The menu flow chart and the setup
steps show the setup for the units
with rate and total (DPF75). When
using a unit which has only count
(DPF76) or only rate (DPF78)
several menu items will not be
displayed.
1. Recheck power wiring
1. Use a different power supply or
install a surge suppressor.
1. Recheck input wiring.
2. Recheck scale factors and factor
calculations.
3. Replace transmitting device.
4. Recheck debounce filtering selection
"hi cps" or "lo cps".
5. To confirm set scale factors at one
and connect a wire to pin #7 and
touch it to pin # 5 (input A). Each
time pin #5 is touched counter A
should count once. If not, call
OMEGA. (this test will not
work on units with quadrature input)
1. Check scaling factor, if it is correct,
lower the number of significant
figures.
2. Reprogram the unit, be sure to enter
a decimal (enter one and remove it if
a decimal is not desired).
1. Recheck programmed relay duration.
2. Recheck programmed relay
activation mode.
1. If relay outputs are not being used,
set the relays for rate (DPF75 only).
2. Set the relay durations to 00.0.
1. The menu items which do not
appear are not used for the models
without the ratemeter (DPF76) or
without the counter (DPF78).
Therefore, disregard any menu items
which appear on the flowchart and
setup steps, but do not appear on
the unit's display.
Page view 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30

Comments to this Manuals

No comments